PAU-A2600S-HC
- Cooling power:2100/2450W
- Voltage:Three-phase AC 200V
- Installation method:
- Dimensions:H1065xW450xD900mm
- Weight:120kg
Specifications Installing the dimensional
PAU-A2600S-HC | (50/60Hz) | ||||||||
Type | PAU-A2600S-HC | ||||||||
Performance | Cooling capacity (W) | 1200/1400 | |||||||
Heating capacity (W) | 2000 | ||||||||
Humidifying capacity (kg/h) | 5.2 | ||||||||
Temperature control accuracy (℃) | ±0.2 | ||||||||
Temperature setting range (℃) | 20~30 | ||||||||
Humidity control accuracy (%RH) | ±1.0 | ||||||||
Humidity setting range (%RH) | 40~80 | ||||||||
Allowable ambient temperature (℃) | 20~30(Humidity gradient within:±1℃/1h) | ||||||||
Allowable ambient humidity (%RH) | 10~85(Humidity gradient within:±5%/1h)(No condensation) | ||||||||
Blower fan air discharge rate (m3/min) | 8.0/8.5 | ||||||||
External | Outside dimensions(H×W×D) (mm) | 1065 × 450 × 900 | |||||||
Weight (kg) | 120 | ||||||||
Paint color | Munsell 5Y 7/1 Equivalent color of light beige | ||||||||
Blower duct joint diameter (mm) | Φ150 | ||||||||
Power Supply | Power supply (V) | 三相 AC200 | |||||||
Operating current | MIN (A) | 5.0/4.7 | |||||||
MAX (A) | 41.5/41.9 | ||||||||
Power consumption | MIN (A) | 920/1100 | |||||||
MAX (A) | 15000/15000 | ||||||||
Water supply and drainage | Humidifier | Water supply (l/h) | 11.7 | ||||||
Water supply pressure (MPa) | 0.03~0.5 | ||||||||
Water supply temperature (℃) | 0~50 | ||||||||
Water supply pipe connection | 15A | ||||||||
Drain pipe connection | 20A | ||||||||
Coolant | HFC-134a 285g | ||||||||
Exhaust air volume (m3/min) | 10.0/12.0 | ||||||||
Protective devices | Main circuit | Ground leakage breaker(50A 30mA) | |||||||
Blower fan(For cooler) | Overcurrent relay、Delay timer(for 3 minutes)、Surgr-absorbing unit | ||||||||
Compressor | Overcurrent relay、Motor protector、Surgr-absorbing unit Low temperature operation prevention thermostat | ||||||||
Heater | Overheat protection thermostat、Temperature fuse、Surgr-absorbing unit | ||||||||
Humidifuer | Float switch、Bimetal thermostat、Temperature fuse、Automatic drain timer、Manual drain switch、Surgr-absorbing unit | ||||||||
External Output | Unit abnormality | a contact: No voltage (AC250V/ 3A /Load resistance) | |||||||
Temperature alarm | a contact: No voltage (AC250V/ 3A /Load resistance) | ||||||||
Humidity alarm | a contact: No voltage (AC250V/ 3A /Load resistance) |
Notes:1.The date of cooling capacity is obtained at an ambient temperature of 25℃ and an ambient humidity of 40%.(With heat insulating duct)
2.The rated tamperature and humidity control accuracy may not be satisfied depending on the ambient temperature and hunidity.
3.When the ambient temperature drops to 18℃ or below, the protective device is activated, automatically stopping the operation of the compressor only and turming off the COMP LED.
4.The protective device and compressor are reset automatically when the ambient temperature rise to 20℃ or above.(* The alam device will not be activated.)
5.Be sure to attach a strainer (accessories) to the water supply side.
6.For the drain pipe, use a material with a heat resistance of at least 100℃. (Heat-resistance vinyl chloride tubing is appli-cable.)
7.For the power cable,use a cable of 22 mm2 or larger size.
8.The PAU unit comes to a complete stop automatically after post-operation of the blower fan is performed for 3 minutes.The operation SW stop precedes post-operation and full stop.
9.When the air volume discharged from the duct tip decreases to 9/10 [m3/min.] or less by connecting a duct, connect an auxiliary fan.
10. Temperature control accuracy is determined according to JTMKO1 constant temperature and humidity - Performancetest method and performance indication method (China Testing Machinery Association). Thermal interference by duct or other parts is not covered under warranty.
11.The noise value above is the maximum value measured at the front, back, right, and left 1 m away from the main unit with a weight of A.