ENC-A1622L
- Cooling power:1450W
- Voltage:Single-phase AC 220V
- Installation method:Side-mount
- Dimensions:H1000×W400×D230mm
- Weight:40kg
Specifications Installing the dimensional
CCC型 ENC-A1622L | (50Hz) | ||||||||
Model | ENC-A1622L | ||||||||
Performance | Cooling capacity (W) | 1450 | |||||||
Settingtemperature range (℃) | 25~45 | ||||||||
Use Area temperature (℃) | 20~50 | ||||||||
Use Area humidity (%RH) | 10~85(No condensation) | ||||||||
External | External dimensions (H×W×D)(mm) | 1000 × 400 × 230 | |||||||
Weight (kg) | 40 | ||||||||
Coating color | Munsell 5Y 7/1 Equivalent color of light beige | ||||||||
Power Supply | Rated voltage (V) | Single-phase AC220V | |||||||
Consumption current | Rating (A) | 2.8 | |||||||
MAX (A) | 3.6 | ||||||||
Starting current (A) | 20.0 | ||||||||
Power consumption | Rating (W) | 550 | |||||||
MAX (W) | 750 | ||||||||
Protection | Noise resietance | Fast Transient / LEVEL4 buy burst immuntiy test | |||||||
Vibration resistance | 5Hz frequency 20mm total amplitude | ||||||||
Dust & Water protection grade | IP54 Equivalent to internal circulation toute | ||||||||
Coolant | R-134a 430g | ||||||||
Noise (dB) | Approx.70 | ||||||||
External Output | Alarm output(a contact:No-voitage resistive load 250V 2A) | ||||||||
Display | Panel internal temperature/Eror code LED,RUN LED | ||||||||
Regulatroy Compliance | CCC | ||||||||
Environmental Response | RoHS |
Notes:Cooling Capacity: Rated capacity value when external temperature is 35℃,intelal temperature is 35℃.(Measurement condition:JIS-C-9612 air enthalpy method)
Ambient humidity / ambient temperature is not meant to satisfy all conditions in temperatuer and hunidity.
MAX Value:Ambient temperature at the time of use is the maximum allowable ambient temperature,when ambient humidity at the time of use is RH 40%.
Noise Resietance: Required for CE marking.
Please read instructions carefully before use,please use properly.