ENC-AR1120L
- Cooling power:950/1100W
- Voltage:Single-phase AC 200V
- Installation method:Side-mount
- Dimensions:H730×W300×D230mm
- Weight:23kg
Specifications Installing the dimensional
ENC-AR1120L | (50/60Hz) | ||||||||
Model | ENC-AR1120L | ||||||||
Performance | Cooling capacity (W) | 950/1100 | |||||||
Setting temperature range(℃) | 25~45 | ||||||||
Use Area temperature (℃) | 20~50 | ||||||||
Use Area humidity (%RH) | 10~85(No condensation) | ||||||||
External | External dimensions (H×W×D)(mm) | 730 × 300 × 230 | |||||||
Weight (kg) | 23 | ||||||||
Coating color | Munsell 5Y 7/1 Equivalent color of light beige | ||||||||
Power Supply | Rated voltage (V) | Single-phase AC200V | |||||||
Consumption current | Rating (A) | 2.6/2.4 | |||||||
MAX (A) | 3.1/3.2 | ||||||||
Starting current (A) | 7.5/7.1 | ||||||||
Power consumption | Rating (W) | 440/460 | |||||||
MAX (W) | 560/570 | ||||||||
Protection | Vibration resistance | Total amplitude:20mm,Frequency:5Hz | |||||||
Dust and drip protection | Approx.IP54(Internal circulation path) | ||||||||
Applied Standard | Low voltage directive:EN60335-1 EN60335-2-40/EMC directive:EN64000-6-2 EN61000-6-4 | ||||||||
Coolant | R-134a 230g | ||||||||
Noise (dB) | Approx.64/68 | ||||||||
External Output | Alarm output(a contact:No-voitage resistive load 250V 2A) | ||||||||
Display | Panel internal temperature/Eror code LED,RUN LED | ||||||||
Environmental Response | RoHS Directive |
Notes:Cooling capacity: the related value when the ambient temperature is 35℃ and the panel intelal temperature is 35℃. (Measurement condition: simple indoor side air enthalpy testing method based on JIS-C-9612)
Rated value:35℃ ambient temperature,ambient humidity RH 40%.
MAX value:Ambient temperature at the time of use is the maximum allowable ambient temperature,when ambient humidity at the time of use is RH 40%.
Please read the instruction carefully before useing and use it correctly.